Greencisco Industrial Co., Ltd.

48V LiFePO4 lithium battery for Telecom,UPS,Solar

Widely used for Telecom,UPS,solar,datacenter,ect. Environment friendly and green energy; Battery life at 25C is 15 years; Deep cycles: 6500 cycles; With RS232,RS485,CAN communication ports; With 19" rack mount design; Working temperature:-20C-+55C

Characteristics

Application:
Telecom,UPS,solar,datacenter,ect.
Made with high quality materials and high-accuracy BMS system.
With large current output with high efficiency and safety
Batteries are with all different kinds of protection functions to make battery  life more longer.
With high performance of charging and discharging.
Environment friendly and green energy Battery life at 25C: 15 years
Deep cycles: 6500 cycles
With RS232,RS485,CAN communication ports
With SOC,SOH display and PC software for operation With parallel function for more capacity
Maintenance free function
With 19" rack mount design
Working temperature:-20C-+55C
Specification 

Basic

specification

Name

LiFePO4 batteries for Solar,Telecom,UPS power,ect

Model

GRLFP-4850

GRLFP-48100

GRLFP-48120

GRLFP-48150

GRLFP-48200

GRLFP-48250

Battery core

C20/3.2V/50AH

Rated voltage

48V

48V

Rated capacity

50AH

100AH

120AH

150AH

200AH

250AH

Battery

constructure

Wideth(mm)

400

450

550

550

550

550

Length(mm)

482.6

482.6

482.6

482.6

482.6

482.6

Height(mm)

130.5

175

222

222

444

444

Weight(kgs)

30.4

50.3

60.5

76.5

104

130

Electrical

specification

Charge mode

Constant voltage/current(CC-CV)

Charge current

0.2C(standard),0.5C in Maximum

Charge voltage

52V-54.4V

52V-54.4V

Discharge mode

Constant current/voltage/capacity(CC/CV/VP)

Discharge current

1C(In Maximum)

Cutoff voltage

42V

42V

Work

condition

Working

temperature

Charging: 0-45℃;Discharging:20℃<0<50℃

Storage

temperature

short time: 10℃<0<45℃ , for less than 3 months, SOC:30%-60%;

long-time storage:10℃<0<40℃ , for less than 12 months, SOC:30%-60%;

Humidity

10%fo-r85%     3 months

Voltage range

42-54.4V;SOC:30%-50%

42-54.4V;SOC:30%-50%

BMS

Overcharging

voltage protection

3.6V for single cell

Overdischarging   voltage protection

2.8V for single cell

Overdischarging

current protection

1.0C

Recovery

Disconnection of load, charging battery

Communication interface

RS232 or RS485 or CAN